Consent — largely solved
- Share of freehold, and you are a director of the company. That removes the slowest and least predictable item on the list. You still want the company’s agreement minuted rather than assumed, but you are asking colleagues, not a landlord with no incentive to reply.
- Exclusive use of the garden and the side passage. Both ground-level positions are yours to use. No demise argument to have.
- The roof needs the other owners, which makes it the slow option rather than the impossible one.
Permitted development — available
- No heat pumps in the building, so yours is the first — which is the one that qualifies. Confirmed.
- Four flats and nothing commercial, so the block is wholly residential and the right applies.
- Conservation area is the last open question, and it takes about a minute. Search your council’s planning constraints map by postcode, or the planning portal for your borough — most publish an interactive layer. It would not stop the installation; it would stop the unit going on any wall or roof fronting a highway, which the garden position avoids anyway.
Going first uses up the building’s allowance
- Only the first installation in the building is permitted development. Once yours is in, the other three flats each need a full planning application to fit one.
- That is worth knowing as a director rather than discovering later. It is not a reason to hold off — the allowance goes to whoever moves first either way — but it is the kind of thing that causes friction at an AGM in three years if nobody was told.
- There is a constructive version: raise it now, and if another flat is thinking about it, a joint application or an agreed position for future units is far easier to get through than four separate ones later.
Permitted development, as it applies to a flat
| Condition | Flat |
| Maximum unit volume, including any housing | 0.6 m³ |
| … for comparison, a house | 1.5 m³ |
| Installations qualifying as PD | first only |
| Noise limit, MCS 020 | 37 dB |
| Old 1 m boundary rule | removed 2025 |
| Flat roof — distance from the edge | ≥ 1 m |
| Pitched roof | not allowed |
0.6 m³ is the constraint people miss. A flat gets less than half the volume allowance a house does, and it includes any acoustic housing you add to pass the noise test. Most domestic monoblocs land between 0.3 and 0.5 m³ — so it is achievable, but it rules out the larger units and it means an acoustic enclosure has to be counted, not bolted on as an afterthought.
Noise is measured at your neighbour’s window
- The limit is 37 dB LAeq,5min, measured 1 m outside the centre of a neighbouring habitable room door or window — not at your boundary, and not at your own wall.
- The 1 m boundary rule was removed in 2025, which gives you more placement freedom than older guidance suggests. From 28 May 2026 MCS 020 is the only certification route the Planning Portal recognises, so the calculation is now the test.
- The side passage is the wrong instinct. A narrow passage between two buildings is a reflective corridor — sound bounces rather than disperses, and a neighbour’s window is likely to be close and directly in line. The garden will almost always calculate better than the passage, even if the passage looks tidier.
- Ask any installer for the MCS 020 calculation with the assessment positions marked, not a verbal assurance. It starts from the manufacturer’s sound power data and it either passes or it does not.
The grant
- The Boiler Upgrade Scheme is £7,500 for an air source heat pump. The £9,000 rate that runs to March 2027 is only for off-gas-grid properties, so it does not apply here — you are on gas and taking it out.
- Conditions: own the property, be replacing a fossil fuel system (your boiler qualifies), and use an MCS-certified installer in an approved consumer code. The installer claims it and deducts it from the quote — you never handle the money.
- There is no mandatory insulation or EPC condition attached to the grant as it stands, though installers will often recommend fabric work first anyway.
- Leasehold is not addressed in the headline guidance — worth confirming with the installer early, because it interacts with the freeholder consent question rather than replacing it.
Cooling — and why it is a heating decision
- You have to decide this now, not later. Only the first outdoor unit in the building is permitted development. Fit an air-to-water heat pump now and bolt a separate air conditioning system on in two years, and that second outdoor unit needs a full planning application — on a building where you have already used the allowance.
- That is the real efficiency you were hoping for, and it is bigger than any equipment saving: one outdoor unit, one planning allowance, one set of pipework, one set of holes in the wall.
What actually cools the flat
| Route | Cools? | Outdoor units |
| Reversible air-to-water + fan coils | yes, properly | 1 |
| Reversible air-to-water + underfloor only | barely | 1 |
| Air-to-water for heat, separate air-to-air for cooling | yes, best | 2 |
- Underfloor cooling does not really work, and it is worth saying plainly. The floor cannot go below the dew point or it condenses, which caps output at roughly 15–25 W/m² — less again through an engineered board. Against a room with large glazing at 60–100 W/m² of load, that is about 0.8 kW of cooling against a 2.7 kW load across both rooms. It takes the edge off a warm evening. It is not air conditioning.
- Worse, condensation under a timber floor is exactly the failure you do not want. Underfloor cooling and engineered wood is a combination most manufacturers will not warrant.
- Fan coils are what actually cool — they dehumidify as well as cool, which is most of what makes a room feel comfortable. They are visible boxes and they need a condensate drain, which is a thing to plan while the floor is open, not after.
The spec changes if cooling is in scope
- Pipework insulation. Heating-only insulation is about stopping heat loss. Cooling pipework must be vapour-sealed or it sweats and drips inside walls and floors. Different, more expensive spec — and if you install heating-grade now and add cooling later, much of it has to come out.
- Condensate drainage to every fan coil position.
- The heat pump itself must be a reversible model, and not all are. This narrows the shortlist, and it interacts with the sound power question — you want a quiet reversible unit, which is a smaller list again.
- Check the grant. Reversible units are generally eligible for the Boiler Upgrade Scheme, since it is assessed on the heating and hot water function — but confirm with the installer before assuming.
The cheaper half of the answer
- Two full-height windows on external walls will drive the summer temperature more than anything the plant does. External shading or solar-control glazing removes heat before it arrives, costs nothing to run, and reduces the cooling capacity you need to buy.
- Ground floor with a garden also means night purge ventilation is available to you in a way it is not for an upstairs flat. Openable windows at both ends of the space, used overnight, do real work in a London summer.
- Do these first and the cooling system gets smaller, quieter and cheaper. Do them second and you have bought capacity you did not need.
The flat is bigger than the drawings
- The lease plan shows a full flat — reception, kitchen, several bedrooms, bathroom and corridor, plus a large tapering garden. Everything drawn so far covers roughly 38 m² of it. The heat pump sizes for the whole flat, not the renovated part, so the heat loss calculation has to cover rooms nobody is otherwise touching.
- Two good pieces of news from it: the garden is generous and tapers away, which gives you all the distance the noise calculation could want; and the demise is clear.
- The communal strip is a fire escape route, and the unit would sit further down in your exclusive area — so no conflict. Worth noting for the installer though: nothing can be stored or sited so it narrows an escape route, including during the works, and that includes pipe runs at low level.
The hidden cost: the radiators you are not replacing
| Flow / return | Output | Radiator size needed |
| 75 / 65 — your boiler today | 100% | ×1.0 |
| 55 / 45 | 51% | ×1.9 |
| 50 / 40 | 41% | ×2.5 |
| 45 / 35 | 30% | ×3.3 |
- Underfloor in the living and kitchen, radiators everywhere else is a mixed system, and the radiators are what set the flow temperature for the entire flat. A heat pump running at 45°C to satisfy an undersized radiator is running at 45°C for the underfloor too, every day, for twenty years.
- Existing radiators sized for a 75°C boiler deliver roughly a third of their rated output at heat pump temperatures. Most will need replacing with something two to three times larger — in bedrooms and a corridor that are not otherwise part of this renovation. That is likely the largest unbudgeted item in the heating plan.
- The alternative is running the system hot enough for the old radiators, which quietly costs you 20–30% on every unit of heat for the life of the system. It is the classic way a heat pump ends up with a bad reputation.
- Worth asking for the heat loss calculation to state, room by room, what flow temperature each existing radiator would need. That single column tells you which ones actually have to change.
Can underfloor replace the 3 m radiator?
| Heatable floor | m² |
| Main room, once the laundry goes | 31.8 |
| Less the three kitchen runs | −3.9 |
| Less the party-wall build-in | −4.3 |
| Actually heatable | 23.7 |
| Output | W/m² | kW |
| Realistic, low profile under timber | 50–70 | 1.2 – 1.7 |
| Theoretical ceiling at a 29°C floor | 85 | 2.0 |
| What the radiator does now, roughly |
| If it is a single panel | — | 2.5 |
| If it is a double | — | 4.5 |
- The built-in joinery eats a quarter of the floor. Underfloor cannot go beneath fixed units, so 31.8 m² of room is 23.7 m² of heated floor. That is the number nobody quotes and it is why floor-only schemes come up short.
- On these figures underfloor alone probably does not replace that radiator. Best case it matches a single panel; against a double it is roughly half. The radiator is very likely oversized for the real heat loss — most are — but the gap is too big to assume away.
- Two full-height windows, garden doors and a solid-wall Victorian half do not help. Fabric first genuinely changes this answer: bring the heat loss down and the floor becomes sufficient. Leave it and you are choosing between a cold room and a hot floor.
The fan coil is the answer to the radiator
- You are already considering a fan coil in the living area for cooling. The same unit heats. That is the elegant resolution: underfloor carries the base load, the fan coil covers the coldest days, and the 3 m radiator still goes.
- It also fixes underfloor’s real weakness, which is response time. A low-profile system under timber is slow; a fan coil brings the room up in minutes when you want it.
- And it means the cooling spend is not a luxury line item — it is doing structural work in the heating design. That materially changes how the cooling budget reads.
- Practical consequence: the fan coil position needs deciding with the joinery, not after. It wants to be high, out of the party-wall build-in, and it needs a condensate drain.
The dining room floor stays down
- So no underfloor there, and its radiator stays — which means it is one of the emitters that will need upsizing for heat pump flow temperatures. In a room where the murphy bed takes 165 of the 178 wall, finding space for a radiator two to three times bigger is not trivial. Worth checking early, because it competes with the bed.
- You are replastering and re-skirting in there anyway. Run conduit at skirting level while it is open — not for underfloor, but for a future fan coil or a relocated emitter. Cheap now, disruptive later.
- With the dining floor staying down, the living and kitchen floor is the only open floor in the flat. Everything that ever needs to cross the building has to be laid there, or through the hall.
The priority order runs backwards to the works
| Priority | Zone | Floor open? |
| 1 | Living / kitchen | yes |
| 2 | Front room | no |
| 3 | Front room | no |
| 4 | Other room | no |
| 5 | Dining | no — floor stays down |
- Only one floor opens, and it is priority 1. Every other zone — including the dining room you are renovating — keeps its floor. So four of five zones can only ever be served through the hall.
- The hall is the pinch point. The plant and the cylinder are at the back; the front rooms are at the front; everything has to cross the hall, and the hall is not in scope. Once both renovated rooms are finished, the hall floor is the only route left and it means lifting a finished floor to serve a finished room.
- So channel the hall now. One strip of hall floor lifted while everything either side is already open, with pipe, conduit and a condensate route laid in and capped, is cheap. Doing the same job in two years costs the hall floor, the front rooms’ skirtings and a fortnight. This is the highest-value thing on this page and it is not a heating decision, it is a five-metre channel.
- Then fit fan coils to priority 1 only if budget is tight. It is the most glazed and most occupied space, cool air migrates, and the stubs are waiting for the rest.
What already constrains the design
- Low-profile underfloor, not screed — forced by the 2200 bulkhead. Less output per m² and far less thermal mass than installers usually assume.
- Engineered board under 18 mm, to stay under 0.15 m²K/W.
- Cylinder boxed in at roughly 520 × 860 — about 180 litres in a shape most heat pump cylinders are not made in. Coil surface area needs checking for low flow temperatures.
- Two full-height windows on external walls in the coldest corner, which will dominate the kitchen’s heat loss.
This week, in order
- Measure the passage width, and pace to the nearest window across the fence.
- Get a whole-flat room schedule together — every room, its floor area, and the size and type of the radiator in it. That is the input for the heat loss calculation and it is the thing that decides the flow temperature.
- Then, and only then, get two MCS installers to quote — each with the MCS 020 calculation and a room-by-room heat loss, not a rule-of-thumb size.
Why this order
- Three of these are binary and none of them are engineering. If the block already has a heat pump, or the freeholder says no to plant on the wall, the system design was wasted work.
- The supply question is the only one with a months-long tail. Everything else can be compressed; a DNO upgrade cannot.
- The heat loss calculation, emitter sizing and cylinder specification all follow once the unit has a legal home and the supply is known. None of them are hard; they are just downstream.
Three positions, re-ranked
- Side passage — back in contention. I had it as a reflective corridor between two buildings. It is not: your building on one side, a fence on the other, a garden beyond. That is open on one flank, so sound disperses rather than bouncing, and a solid fence close to the unit is a genuine acoustic barrier toward the neighbouring garden — barriers work best when they break the line of sight near the source. It is also by far the shortest pipe run to the cylinder in the kitchen’s north-west corner.
- Garden — still the safe answer. Most distance from every assessment position, no width constraint, easiest to service. Costs you pipe run and takes up garden.
- Extension roof — still third. Needs the other owners, a structural check, and 1 m from every edge. The real objection is unchanged: it sits directly above your own rooms, so you would trade your neighbours’ airborne noise for your own structure-borne vibration.
What the passage needs to clear
- Width. A monobloc typically wants around 1 m clear in front of the discharge fan and 300 mm behind and to the sides. Add the unit’s own depth and you need roughly 1.5 m of passage, still leaving room to walk past to the garden. Worth measuring before anything else — it is a hard yes or no.
- Your own kitchen windows are right there. Two full-height ones on that wall. They are not assessment positions — MCS 020 only looks at neighbouring dwellings — so this will not fail the calculation. It will just be your own kitchen you are running a fan outside. Worth siting it away from the window rather than under it.
- Keep it clear of the hob duct. The venting hob discharges through that same wall. Grease-laden air onto an evaporator coil fouls the fins and kills efficiency. They need to be well apart, and ideally the heat pump upwind of the extract rather than downstream of it.
- The basement flat is still the deciding factor. If it has a window or lightwell onto the passage, the passage is out regardless of how open it is.
The basement, resolved
- The basement is only under the front half, and its windows sit below the new dining room — the front end of the flat. So the garden has nothing beneath it, and the garden end of the side passage is clear of them.
- That is what makes the passage viable: put the unit at the kitchen end, nearest the garden, and the basement windows are at the far end. Shortest pipe run to the cylinder and the greatest distance from the hardest assessment position, which rarely line up this neatly.
The assessment positions that remain
- Every other flat in the building is a neighbour for the noise assessment — MCS 020 measures 1 m outside the centre of a neighbouring habitable room window, and all four flats are separate dwellings.
- The two above look down on the garden, which helps: distance and angle both work in your favour.
- The basement is the exception that would have decided it — but it is at the front, so it stops being the binding constraint. The ground-floor neighbour across the fence is now the position to check, since their windows are at the same level as the unit.
- So the first thing to look at is where the basement flat’s windows actually are. If they face the street rather than the garden, this gets much easier. If they open onto the garden, the unit needs to be as far from them as the plot allows.
1 m is not the clearance — it is the measuring point
- Worth being precise, because it is the most common misreading of the rule. The 1 m is where the measurement is taken — 1 m outside the centre of the neighbour’s window. It is not a distance you have to keep clear.
- The actual test is that the calculated level at that point is 37 dB or below. For a typical unit that means three to six metres of separation, not one.
How far is far enough
| Unit sound power | Open ground | Against a wall | In a corner |
| 50 dB(A) | 1.8 m | 2.5 m | 3.5 m |
| 52 dB(A) | 2.2 m | 3.2 m | 4.5 m |
| 55 dB(A) | 3.2 m | 4.5 m | 6.3 m |
| 58 dB(A) | 4.5 m | 6.3 m | 8.9 m |
| 61 dB(A) | 6.3 m | 8.9 m | 12.6 m |
| 65 dB(A) | 10.0 m | 14.1 m | 20.0 m |
Indicative only — simple point-source geometry, not the MCS 020 method, which adds barrier corrections and its own margins. Use it to sanity-check an installer’s proposal, not to replace their calculation. A unit in the passage counts as against a wall at best.
- This makes sound power a selection criterion, not a footnote. Going from a 61 dB(A) unit to a 55 dB(A) one halves the distance you need. That is the difference between the passage working and not working, and it is decided when you choose the model — not afterwards.
- Ask for the sound power level at the rated condition, and check whether the quoted figure depends on a night or quiet mode that also cuts output. A unit that only passes in quiet mode passes on paper and struggles in January.
The trade you are actually making
- Distance from windows buys you the noise calculation. Every metre also costs you heat in the pipe run and money in insulated pipework, because the cylinder sits at the far south-west corner of the flat.
- So the useful thing to know next is how deep the garden is, and where the upstairs flat’s windows are. Those two facts between them decide the position, and neither takes long.
Honest risks to November
- DNO upgrade if the fuse is 60 A — but the 100 A switchgear suggests a fuse swap rather than a new service. Downgraded from months to probably weeks.
Planning application — permitted development applies, subject only to conservation area status.
Freeholder consent — resolved. Share of freehold and you are a director.
- Squat cylinder availability — a niche product. If it cannot be sourced, the kitchen corner design changes.
- MCS installer availability — autumn is their busy season, and the grant means demand outstrips supply.