Heating & cooling

Consent is resolved and permitted development applies. What is left is where the unit goes, whether the noise calculation passes, and whether cooling is in scope — which has to be decided now rather than later. Electrical has moved to its own page.

Consent — largely solved

Permitted development — available

Going first uses up the building’s allowance

Permitted development, as it applies to a flat

ConditionFlat
Maximum unit volume, including any housing0.6 m³
… for comparison, a house1.5 m³
Installations qualifying as PDfirst only
Noise limit, MCS 02037 dB
Old 1 m boundary ruleremoved 2025
Flat roof — distance from the edge≥ 1 m
Pitched roofnot allowed
0.6 m³ is the constraint people miss. A flat gets less than half the volume allowance a house does, and it includes any acoustic housing you add to pass the noise test. Most domestic monoblocs land between 0.3 and 0.5 m³ — so it is achievable, but it rules out the larger units and it means an acoustic enclosure has to be counted, not bolted on as an afterthought.

Noise is measured at your neighbour’s window

The grant

Cooling — and why it is a heating decision

What actually cools the flat

RouteCools?Outdoor units
Reversible air-to-water + fan coilsyes, properly1
Reversible air-to-water + underfloor onlybarely1
Air-to-water for heat, separate air-to-air for coolingyes, best2

The spec changes if cooling is in scope

The cheaper half of the answer

The flat is bigger than the drawings

The hidden cost: the radiators you are not replacing

Flow / returnOutputRadiator size needed
75 / 65 — your boiler today100%×1.0
55 / 4551%×1.9
50 / 4041%×2.5
45 / 3530%×3.3

Can underfloor replace the 3 m radiator?

Heatable floorm²
Main room, once the laundry goes31.8
Less the three kitchen runs−3.9
Less the party-wall build-in−4.3
Actually heatable23.7
OutputW/m²kW
Realistic, low profile under timber50–701.2 – 1.7
Theoretical ceiling at a 29°C floor852.0
What the radiator does now, roughly
If it is a single panel—2.5
If it is a double—4.5

The fan coil is the answer to the radiator

The dining room floor stays down

The priority order runs backwards to the works

PriorityZoneFloor open?
1Living / kitchenyes
2Front roomno
3Front roomno
4Other roomno
5Diningno — floor stays down

What already constrains the design

This week, in order

Why this order

Three positions, re-ranked

What the passage needs to clear

The basement, resolved

The assessment positions that remain

1 m is not the clearance — it is the measuring point

How far is far enough

Unit sound powerOpen groundAgainst a wallIn a corner
50 dB(A)1.8 m2.5 m3.5 m
52 dB(A)2.2 m3.2 m4.5 m
55 dB(A)3.2 m4.5 m6.3 m
58 dB(A)4.5 m6.3 m8.9 m
61 dB(A)6.3 m8.9 m12.6 m
65 dB(A)10.0 m14.1 m20.0 m
Indicative only — simple point-source geometry, not the MCS 020 method, which adds barrier corrections and its own margins. Use it to sanity-check an installer’s proposal, not to replace their calculation. A unit in the passage counts as against a wall at best.

The trade you are actually making

Honest risks to November